Product description:
The air-cooled chiller features:
Refrigeration heart with fully sealed low noise, vibration small, high-performance power-saving imported brand-name compressor, electrical control all adopt imported brand-name original, heat exchangers, shell and tube condenser heat exchanger performance, ease of cleaning and maintenance.
Energy Economy:
Digital electronic thermostat accurately control the cold water temperature between +3 ℃ to 50 ℃, so as to control the unit normal operation, ensure the unit to save energy, and assembly of all the units, internal wiring, refrigerant filling and commissioning are completed in the factory, this section models can be ordered hot and cold dual-use.
Safe operation:
Fuselage equipped with compressor delay start protection, over-current relay, high and low voltage protection, fuse plugs, electronic time protect the safety valve to ensure the normal operation of the unit.
Condenser:
* Steel tube aluminum heat exchanger for the air-cooled condenser, the design and manufacture of single-loop and multi-loop coil designed to increase the heat transfer area than standard, uniform surface wind speed, stable heat transfer efficiency lasting.
* Use a high efficiency of rebar pipe, both ends of the cover interchangeable to pay more then the direction of water pipes, plumbing processes multi-loop, the condenser and compressor capacity co-ordination, straight-through water pipes are easy to clean and maintenance.
Air-cooled chiller (a) Specifications / SPECIFICACATIONS |
Parameters Parameter |
Model Model |
SCY-1/2A |
SCY-01A |
SCY-02A |
SCY-03A |
SCY-04A |
SCY-05A |
SCY-06A |
SCY-08AD |
Cooling capacity
Cooling Capacity |
Kw
50Hz/60Hz |
1.53
1.79 |
2.94
3.44 |
5.67
6.63 |
8.39
9.82 |
10.9
12.75 |
13.95
16.32 |
16.9
19.77 |
21.8
25.51 |
Kcal / h
50Hz/60Hz |
1316
1540 |
2528
2958 |
4872
5701 |
7216
8442 |
9374
10968 |
11990
14028 |
14530
17000 |
18748
21935 |
Total input power
Total input |
KW |
0.68 |
1.31 |
2.6 |
3.6 |
4.5 |
5.5 |
6.6 |
8.6 |
Maximum operating current
Maximum Running Current |
A |
4.1 |
8 |
15.8 |
8.8 |
10.9 |
13.4 |
16 |
20.9 |
Power Power Supply |
Volt |
1N-220V 50Hz/60Hz |
3N-380V/415V 50Hz/60Hz |
Refrigerant Refrigerant |
Name Name |
R22 |
Filling amount of Fill |
Kg |
0.6 |
0.8 |
1.8 |
2.7 |
3.5 |
4.3 |
5 |
3.5x2 |
Control type of control method |
Capillary Capillary Tube |
Compressor Compressor |
Type Type |
Hermetic rotary
Hermetic Rotary |
Full rotation or piston closed vortex
Hermetic Scroll or Piston |
Power Motor |
Kw |
0.55 |
0.75 |
1.5 |
2.25 |
3 |
3.75 |
4.5 |
3x2 |
Cooling air volume Air Flow |
m3 / h |
800 |
1000 |
2000 |
3000 |
4000 |
5000 |
6000 |
8000 |
Chilled water Chilled
Water |
Water Flow |
m3 / h |
0.26
0.31 |
0.51
0.59 |
0.97
1.14 |
1.44
1.68 |
1.87
2.19 |
2.4
2.81 |
2.91
3.41 |
3.75
4.39 |
Tank Tank |
m3 |
0.022 |
0.028 |
0.038 |
0.038 |
0.065 |
0.065 |
0.11 |
0.11 |
And out of the water pipe diameter
In / Out pipe size |
G1 / 2 " |
G1 / 2 " |
G3 / 4 " |
G3 / 4 " |
G3 / 4 " |
G1 " |
G1 " |
G1 "-1 / 2" |
Pumps Pump |
Power Motor |
Kw |
0.375 |
0.375 |
0.55 |
0.55 |
0.55 |
0.75 |
0.75 |
0.75 |
Pressure Pressure |
KPa |
180 |
180 |
250 |
242 |
242 |
290 |
290 |
290 |
Dimensions
Dimension |
Long Length |
mm |
600 |
600 |
820 |
945 |
945 |
1035 |
1200 |
1470 |
Wide Width |
mm |
400 |
400 |
460 |
550 |
550 |
610 |
650 |
710 |
High Height |
mm |
940 |
940 |
1170 |
1370 |
1370 |
1385 |
1480 |
1700 |
Weight Weight |
Kg |
45 |
60 |
120 |
130 |
160 |
170 |
250 |
270 |
Remarks: |
Cold were based ice water inlet temperature of 12 ° C, the outlet temperature of 7 ° C; cooling water inlet temperature of 30 ° C, the outlet temperature of 35 ° C is calculated. |
|
|
Note: |
1.Nominal cooling capacity conditions: chilled water in 12 ℃, out7 ℃; cooling water in 30 ℃, out35 ℃. |
|
Directory specifications are subject to change without notice. |
|
2.Specifications are subject to change without notice for further improvement. |
Air-cooled chiller (b) Specifications / SPECIFICACATIONS |
|
Parameters Parameter |
Model Model |
SCY-10AD |
SCY-12AD |
SCY-15AD |
SCY-20AD |
SCY-25AD |
SCY-30AD |
SCY-40AD |
SCY-50AD |
SCY-60AD |
Cooling capacity
Cooling Capacity |
Kw
50Hz/60Hz |
28.01
32.78 |
33.79
39.53 |
44.15
51.65 |
59.08
69.12 |
71.72
83.91 |
87.2
102.02 |
113.58
132.89 |
135.49
158.52 |
181.68
218.02 |
Kcal / h
50Hz/60Hz |
24089
28184 |
29059
33999 |
37965
44419 |
50805
59442 |
61683
72169 |
74992
87741 |
97675
114,280 |
116,521
136330 |
156,249
187,499 |
Total input power
Total input |
KW |
11 |
13.3 |
17 |
22.8 |
<, SPAN style = "FONT-FAMILY: Arial; FONT-SIZE: 9pt"> 27.7 |
33.7 |
42.8 |
51.1 |
68.8 |
Maximum operating current
Maximum Running Current |
A |
26.7 |
32.3 |
41.3 |
55.4 |
63.1 |
76.8 |
97.5 |
116.5 |
143.1 |
Power Power Supply |
Volt |
3N-380V/415V 50Hz/60Hz |
Refrigerant
Refrigerant |
Name Name |
R22 |
Filling amount of Fill |
Kg |
4.3x2 |
5x2 |
6.5x2 |
8.5x2 |
10.5x2 |
12.5x2 |
17x2 |
20.5x2 |
24.9x2 |
Control method
control type |
Capillary
Capillary Tube |
The outside balanced hot skill expansion valve
With hermetic gyral or piston |
|
Compressor
Compressor |
Type
Type |
Hermetic scroll or piston
With hermetic gyral or piston |
|
Power Motor |
Kw |
3.75x2 |
4.5x2 |
5.5x2 |
7.5x2 |
9.4x2 |
11.3x2 |
15x2 |
18.8x2 |
22.5x2 |
Cooling air volume Air Flow |
m3 / h |
10000 |
12000 |
15,000 |
20000 |
25000 |
30000 |
40000 |
48000 |
66000 |
Chilled water
Chilled
Water |
Water Flow |
m3 / h |
4.82
5.64 |
5.81
6.8 |
7.6
8.89 |
10.16
11.89 |
12.34
14.44 |
15
17.55 |
19.53
22.85 |
23.3
27.27 |
30.52
36.63 |
Tank Tank |
m3 |
0.188 |
0.188 |
0.285 |
0.285 |
0.405 |
0.405 |
0.61 |
0.61 |
0.7 |
And out of the water pipe diameter
In / Out pipe size |
G1-1/2 " |
G1-1/2 " |
G2 " |
G2 " |
G2-1/2 " |
G2-1/2 " |
G3 " |
G3 " |
G3 " |
Pumps
Pump |
Power
Motor |
Kw |
1.5 |
1.5 |
1.5 |
2.2 |
2.2 |
4 |
4 |
4 |
4 |
Pressure Pressure |
KPa |
205 |
205 |
205 |
220 |
220 |
250 |
250 |
250 |
250 |
Dimensions
Dimension |
Long Length |
mm |
1475 |
1460 |
1800 |
1960 |
2080 |
2080 |
2300 |
2300 |
3556 |
Wide Width |
mm |
715 |
800 |
890 |
940 |
1000 |
1000 |
1220 |
2200 |
2200 |
High Height |
mm |
1695 |
1780 |
1880 |
1960 |
2055 |
2055 |
2310 |
2210 |
2210 |
Weight Weight |
Kg |
350 |
370 |
520 |
590 |
790 |
880 |
1100 |
1280 |
1420 |
Remarks: |
Cold were based ice water inlet temperature of 12 ° C, the outlet temperature of 7 ° C; cooling water inlet temperature of 30 ° C, the outlet temperature of 35 ° C is calculated. |